Ac miniature circuit breakers are applicable to the low-voltage terminal distribution. They are used for the short circuit and overload protection, control, isolation and DC system protection. Brand: Nader. Series: NDM1, NDB1, NDB2, NDM1T, NDB1C, NDB2T, NDM1F, NDB6.

Product Description

The Nader series circuit breakers are applicable to the low-voltage terminal distribution in the industry, civil buildings, energy, communication, infrastructure and other fields. They are used for the short circuit and overload protection, control, isolation and DC system protection.

 

NDM1-63 series:

AC230/AC240V (1P); AC400V (2P, 3P, 4P); DC80V (1P, 2P).

Tripping characteristics: Type B: 3ln~5ln, Type C: 5ln~10ln, Type D: 10ln~14ln.

50A and 63A products are not available for the NDM1-63 series Type D product. The breaking capacity of Type B and C products in the NDM1-63 series with the rated current of 1-40A is 6kA, while that of 50A, 63A and Type D product is 4.5kA. Only one type of protection accessories can be assembled on the right side; see the accessory for the specific model and parameters. A maximum of 3 OFs or SDs can be assembled on the left side of each product with the recommended number of assembly no more than 2. If the shunt release accessory is assembled on the right side, the residual current protection accessory or over-voltage/under-voltage accessory can't be assembled.

Protection class is IP20.


Certification

CCC, TUV, RoHS.


Packaging & Delivery

Poles

Quantity (PCS)

HxWxD (mm)

Weight (KG)

1P

12

82×80×220

1.33

2P

6

82×80×220

1.33

3P

4

82×80×220

1.35

4P

3

82×80×220

1.35



NDM1-125 Series:

AC230/AC240V (1P, 2P, 3P, 4P); AC400/AC415V (2P, 3P, 4P); DC60/ DC80V (1P); DC80/DC125V (2P).

Tripping characteristics: Type C 8In (1±20%), Type D 12In(1±20%).

The NDM1-125 circuit breaker has an isolating function with the practical indication of the contact position. Only one type of protection accessories can be assembled on the right side; see the accessory for the specific model and parameters. A maximum of 3 OFs or SDs can be assembled on the left side of each product with the recommended number of assembly no more than 2. If the shunt release accessory is assembled on the right side, the residual current protection accessory or over-voltage/under-voltage protection accessory can't be assembled.

 

Certification

CCC, CE, TUV, UL1077, RoSH.


Packaging & Delivery

Poles

Quantity (PCS)

HxWxD (mm)

Weight (KG)

1P

9

80×94×250

1.60

2P

4

80×94×250

1.43

3P

3

80×94×250

1.60

4P

2

80×94×250

1.43


NDB2-40 series:

AC230/240V (1P+N).

 IP20;


Certification

CCC, CE, CB, TUV, UL1077, ROHS.



NDB2-63K series:

AC230V: 1P+N

IP20,.


Certification

CCC, ROHS.



NDB2-63 series:

The NDB2-63 series has passed the IEC60898-1 (GB10963.1) UL1077 certification with the practical indication function of the contact position. The breaking capacity of the whole NDB2-63 series is 10kA. Only one type of protection accessory can be assembled; see the attachment for the specific model and parameters. A maximum of 3 OF2s or SD2s can be assembled for each product. If the accessory ATM is used, it shall be used together with TM2 and SD2, but TM2 can be used separately.


AC230/240/400/415V (1P); AC400/415 (2P/3P/4P); DC277V (1P), DC60/80V (1P/2P), DC125V 2P.

IP20.


Certification

CCC, CE, CB, TUV, UL1077, RoHS.


Packaging & Delivery

Poles

Quantity (PCS)

HxWxD (mm)

Weight (KG)

1P

12

80×94×250

1.87

2P

6

80×94×250

1.87

3P

4

80×94×250

1.87

4P

3

80×94×250

1.87



NDB2T-63 series:

AC230/240 (1P), AC400/415 (2P, 3P, 4P), DC60/80V (1P), DC80/125V (2P).

IP20.


Certification

CCC, CE, TUV, UL1077, ROHS.


 

NDB2T-63 with UL489 series:

AC120V (1P); 227V (1P, 2P, 3P); 240V (2P, 3P); AC480V (1P, 2P, 3P); DC60V (1P/2P); DC125V (2P).

IP20.


Certification

UL489, ROHS


Packaging & Delivery

Poles

Quantity (PCS)

HxWxD (mm)

Weight (KG)

1P

12

80×94×250

3.00

2P

6

80×94×250

3.00

3P

4

80×94×250

2.67

4P

3

80×94×250

3.00




NDB6-125 series:

AC230/240V (1P), AC400/415V (2P, 3P, 4P), DC60V (4P).

IP20.


Certification

CCC, CE, ROHS.


Packaging & Delivery

Poles

Quantity (PCS)

HxWxD (mm)

Weight (KG)

1P

9

285×125×115

2.13

2P

4

285×125×115

1.91

3P

3

285×125×115

2.13

4P

2

285×125×115

1.91



Auxiliary parts:

Auxiliary PN

Quantity (PCS)

HxWxD (mm)

Weight (KG)

OF Auxiliary contact

10

82×80×220

0.47

OF2 Auxiliary contact

10

82×80×220

0.58

SD Alarm contact

10

82×80×220

0.57